Thought energy from the people at Virtjoule

From the Blog

Summary

Refrigeration faults aren’t always blamed on the condenser or evaporator.  Sometimes there is a perfectly good explanation and a cheap fix.  This article shows the effect on cycle times when a walk-in refrigerator door was accidentally left open overnight after a produce delivery.

Key Concepts

Virtjoule detects extended cycle times that can be due to problems with the walk-in cooler box itself.

When door seal gaskets wear out and doors need an adjustment, the unit will have to work harder to make up for heat leaking into the cooler.

The first chart shows the normal cycle pattern for this Heatcraft HyperCore.  Cycle times are between 8 and 15 minutes long and the unit cycled 33 times.

Normal walk-in cycling pattern

Normal walk-in cycling pattern

The next day, in the early morning hours, the unit began a very long 3 hr and 40 minute cycle followed by a 33 minute cycle, a 47 minute cycle, and two 52 minute cycles.  By that time the morning crew figured out the cause of the problem and got the door closed.

Extended cycle times when door is open

Extended cycle times when door is open

Virtjoule caught this problem through the use of cycle duration rules and recognizing several extended duration cycles.  No crisis call was made to this client because of the early morning time and the fact that the unit was still cycling.

When we see a unit extend cycle times like this, but still cycle off and on, we can safely assume the unit is still meeting demand.  It’s obviously taking a lot longer to meet the demand and the unit should be looked at.

The fix in this case was cheap and obvious…close the door.  Other situations could be more insidious.  Walk-in refrigerator doors are used a lot.  Door seals wear out.  Hinges sag.  Latches break.  When door seals start to fail or the door doesn’t fit as well, it can be hard to know.

When you’re monitoring the cycle count and cycle durations, you can see the unit begin to work harder and harder to make up for the cooling loss.

Summary

Of all the faults that Virtjoule can detect, refrigerant leaks generally give the most warning.  In most cases there is plenty of time to fix the problem before it becomes critical and before you have to spend money on expensive overtime or disrupt your business.

That being said, this article has a unique perspective in that it covers a refrigerant leak that progressed from normal to total failure before being addressed.

Key Concepts

- Refrigerant leaks cause very common behavior changes in a condenser or package unit that can be detected by Virtjoule

- Most refrigerant leaks occur slowly enough that they don’t have to turn into crises

- It’s simple to measure and show that a fix has worked

- Temperature is a lagging indicator of a problem.  By the time temperature control is lost, the failure has already occurred.  Runtime and cycle monitoring can give warnings of impending failure days in advance.

The Setup

I will run through a set of six charts, one per day, that illustrate various phases of runtime behavior that we saw when a walk-in split system was on its way to total failure.

Not surprisingly, refrigerant leaks can occur at various rates.  Some occur over months while others, once developed, can progress over the course of a few days.  We have the luxury of monitoring a unit whose leak progressed at a very specific rate, day by day, over the course of six days, each day exhibiting a new and interesting behavior.

From experience, we see split systems are much more prone to leaks.  This is primarily because there is more custom-installed refrigerant line and longer runs with more field soldered joints. These installations often have to work around difficult building designs, turning several corners along the way.  In many cases a split system may be installed well after the building was built.  Computer room air conditioners (CRAC units) are one example.  Another is restaurants where a new walk-in refrigerator is added to a space that lacked one before.

Package units can also develop refrigerant leaks, but our experience shows us this scenario is rarer.  Because refrigeration circuits are built at the factory, they can be subjected to higher quality standards.  Because the compressors, condenser, and evaporator are all in the same unit, there are fewer things to go wrong and fewer people coming together to make the thing work.  It can more easily be pressure tested before being shipped.

Phase I – Normal Operation

Normal Refrigeration Cycling

Normal Refrigeration Cycling

One of the nice things about 24/7 monitoring is that you can easily determine what is normal.  This is a normal looking cycling pattern for a walk-in condenser unit.  Very regular cycles in lower load times of the day.  Cycle times stretch out a little and intensity increases when the unit is under the most load: from opening at around 9 am through to about 6 pm.

Phase II – Unexplained shutdown for 1.5 hrs

Intermittent Refrigeration Cycling

Intermittent Refrigeration Cycling

On Day 2, we called a fault at around 2 pm because there was a non-operation alert  indicating that the unit had not come on for about an hour and a half, something that was very unusual for this machine.   You can also see that cycle times before the shutdown were much longer than the day before.

The unit started up again on its own.  The next cycle was understandably longer as the unit worked to catch up with the demand caused by no runtime for 1.5 hrs.  Notice that all of the cycles after that were longer than the day before, even when the unit didn’t have as much load.

Phase III – Erratic cycling

Erratic refrigeration cycling

Erratic refrigeration cycling

The slightly elongated cycles continued throughout the next morning.  At 6 am there was another unexplained shutdown which triggered a non-operation alert.  From then on, cycles became much longer with longer shutdowns than normal in between.

By now, even an untrained observer of these graphs could tell you that Day 3 of runtime looks a lot different than Day 1.

Phase IV – Failure begins

Walk-in refrigerator going into failure

Walk-in refrigerator going into failure

Notice that the morning cycles continued at much longer intervals indicating that the unit is still working hard to keep up.  Around 10:30 am, both the intensity jumped as well as the cycle times started to lengthen each and every cycle.  By the middle of the afternoon the unit was running non-stop.

Once a unit is running in a non-stop state like this, the only thing we can tell the customer is that the unit is almost certainly not meeting the cooling demand required.  How long it will be from here before there is a noticeable temperature rise in the cooler depends on a lot of things:  what time of day constant runtime began, how often the walk-in is accessed thereby placing more load on the cooler, whether the walk-in is a freezer or refrigerator, how much product is in the cooler, how big the cooler is, and what the air temperature is outside the cooler.

We get very nervous on behalf of the customer at this point.  The clock is ticking and something should be done — soon.

Phase V – Total Failure

Full failure of walk-in refrigerator

Full failure of walk-in refrigerator

We confirmed for the client the next morning that the unit ran non-stop all night.  We had no reason to believe the situation was going to get better as we’ve seen this degradation pattern a number of times before.  The client confirmed that temperature was rising in the cooler.  They had to crowd all of the product into another unit until the leak could be found and fixed.

The HVAC technician worked on it that afternoon, but had not confirmed the leak yet.  The unit was not restarted.

Phase VI – The Fix

Refrigerant leak fixed.  Catch up and then normal cycling begins

Refrigerant leak fixed. Catch up and then normal cycling begins

By the next day, the leak was located and fixed.  The unit was restarted.  A condenser unit will always run a long time until the cooler reaches the right cold temperature.  This is normal.  By about 6 pm the unit fell back into its normal cycle rhythm and has been running this healthy pattern ever since.

Conclusion

Because normal cycling behavior was well established for this unit, abnormal cycling behavior was very apparent, both to the eye and to our fault detection algorithms.

Unless a refrigerant line is physically damaged, most refrigerant leaks occur over much longer periods of time.  The rate of the refrigerant leak will determine how long the customer has between fixes, if the leak is not found.

Condenser units often have plenty of capacity which is part of why they cycle as much as they do.  A refrigerant leak can go for a quite a while until the condenser unit runs out of capacity to meet heat rejection demand.  The pre-failure phases mentioned above can often be seen over the course of a few days or even a few weeks, giving the client ample time to address the problem before it turns into a crisis.

Temperature monitoring is a lagging indicator of a failure.  By the time temperature control is lost, the failure is already mature and you’ve lost valuable time to get it repaired.  Runtime and cycle monitoring the condenser unit can detect system wide degradation and failure sometimes giving days of warning.  In this case there were indications of a major problem three days before the failure.

 

[Randy Cox - CEO and co-founder of Virtjoule - He is the software designer and analytics engineering for Virtjoule Sense sensors. He studied Chemical Engineering and Petroleum Refining at the Colorado School of Mines. You may contact Randy at: randy at virtjoule dot com]

Summary:

Refrigeration is a critical component of any restaurant for a variety of reasons, not the least is the health and safety of its customers.  Keeping a close eye on how that refrigeration is working is key to avoiding health concerns and potentially the loss of all the contents of a walk-in cooler.  In this article you will see how easy it is to notice that a walk-in refrigeration condenser unit is beginning to malfunction.

Key concepts:

  • Most any kind of fault will disrupt the observable common pattern of how the condenser unit operates.
  • Condenser faults may build up over time wasting energy and working equipment harder before a total failure occurs.
  • There can be adequate time to get a faulty unit fixed before it completely fails if the behavior change caused by the fault is detected.
  • Quick visual inspection of Virtjoule charts to compare patterns can easily identify changes in behavior that need to be investigated.

We recently notified a customer of a behavior change that we observed in the walk-in refrigerator for their restaurant.  This is a critical unit for the restaurant as it’s the condensing unit for the only walk-in refrigerator that they have at this site.  As you will see in this article, it’s not hard to figure out that something had radically changed in the operation of this unit despite the fact that the temperature in the cooler hadn’t risen.  It was just a matter of time before this unit would have failed causing a big problem for the restaurant owner and the manager.

The walk-ins for this restaurant chain are made by Harford Duracool.  Their labels don’t last in the sun and so I don’t have the exact model number for this condenser unit.  The photo below is of the actual unit that failed.

Harford Duracool walk-in refrigerator condenser unit

Harford Duracool walk-in refrigerator condenser unit

What I want you to note in the following graphic is just how easy it is to determine that the unit has broken out of it normal pattern.  This could be done visually or by using the Virtjoule cycle counter which would have shown a radical drop in the number of full cycles that occurred.  The green and red highlights are mine.

You can see that just before 10:00 am on October 30, this unit stopped doing full cycles and ran continuously until about 4pm where it shut down for a few minutes and then started back up with an intense series of cycles only shutting down once every 5-6 hrs.  Clearly this is much different than the cycles you see on the left hand side of the chart.  The unit is working much more aggressively and constantly.

Harford Duracool Condenser breaking into failure pattern

Harford Duracool Condenser breaking into failure pattern

The unit wasn’t fixed right away and luckily there was not a catastrophic failure that would have required moving or throwing away the food in the cooler.  You can see this same failure pattern continued for quite some time.

Harford Duracool condenser in failure mode

Harford Duracool condenser in failure mode

Finally, about 9am on November 11th, the unit was shut down.  It was thawed out, condenser cleaned, and then restarted just after 10:30 am.  It ran continuously for a while in order to catch up on its cooling, but then settled back into its normal cycle rhythm about 6pm.  It has been running normally ever since.

Harford Duracool condenser failure fix

Harford Duracool condenser failure fix

In conclusion, you can see that it’s not at all difficult to notice that there was a problem developing and it was also quite easy to see when the problem was resolved.  Virtjoule didn’t diagnose what the problem was, but it gave enough warning time for the unit to be looked at, fixed, and restarted before a catastrophic failure occurred.  There was no other type of monitoring being done on this unit and it would have completely failed leaving the cooler to warm up at an inopportune time (night, food inspector dropping by, etc.).  Compared to that inconvenience, a call to the Harford Duracool dealer and service was all it took to get things working well again.